Product Type:Digital Output Modules
Nominal Output Voltage:24 VDC
Operational Voltage Range:15 to 30 VDC
Absolute Maximum Output Voltage:33 VDC
Absolute Maximum Reverse Input Voltage:- 0.6 VDC
Switching Output Current:<4.8 A, self-limiting
Degraded Mode Output Current:> 0.7 A, self-limiting
Field Alarms:Loss of field power, output point shorted
On or Off Loop-back Thresholds:0–5 VDC = Off region, 6–14 VDC = transition region, 15–30 VDC = On region
Leakage to Load (Off):Self-limited
Diagnostic (Loss of View):Force-to-value diagnostic (FVD), <2 ms/test
Maximum Input Toggle Rate:<20/sec FVD
Off State Glitch Duration:<2 ms
Magnitude:≈36% test voltage
Output Impedance:0–5 VDC, ≈ 100 kΩ
ADC Scan Time:<1 ms for all 32 points
Functional Earth to Protective Earth Isolation:500 VDC, minimum
Functional Earth to Functional Earth (Logic Ground) Isolation:800 VDC, minimum
Engineered for superior performance and reliability in demanding industrial environments, the Triconex D03401 Digital Output Module ensures consistent and accurate control of processes.
Featuring a wide operational voltage range and robust insulation capabilities, this module is capable of handling a variety of power sources and environments without compromising performance.
With its self-limiting switching and degraded mode current control, the Triconex D03401 is designed to maintain system integrity even under varying conditions, providing peace of mind for operators and engineers alike.
Innovative diagnostic features, including Force-to-Value Diagnostic (FVD), enable quick identification of faults, minimizing downtime and maximizing efficiency.
Offering unparalleled isolation between functional and protective earth, the Triconex D03401 ensures the safety of personnel and equipment, making it an indispensable component in critical control systems.
There are no reviews yet.